Fuels 39
Designation Unit Limit Value Remarks
Fluorine
mg/m³
N
5*
With higher values, consultation with
manufacturer and analysis are necessary
Chlorine + uorine mg/m³
N
10*
With higher values, consultation with
manufacturer and analysis are necessary
NH
3
ppm
70*
With higher values, consultation with
manufacturer and analysis are necessary
* = a non-binding guideline value, where oxidation-type catalytic converters are in use.
Analysis and consultation with MTU necessary.
The limit values are based on a calori c value of 10 kWh/m
3
N
. This corresponds to a reference
to fuels with 100% by vol. methane or, if there are other combustible elements in the fuel, an
equal energy equivalent and thus an equal input of pollutants.
Example:
Russian natural gas with a caloric value of 10 kWh/m
3
N
(Table 14) is used. The permissible value for total
sulfur in the gas thus corresponds exactly to the limit value specied in Table 16.
When using gas from Osthannover, for example, with Hu = 8.15 kWh/m
N
(Table 15) the
permissible max. value of total sulfur is calculated thus:
permissible total sulfur content = 30 mg/m³
N
(8.15 kWh/m
3
N
: 10.0 kWh/m
3
N
) = 24.5 mg/m³
N
No warranty is given in respect of impairment and / or damage (corrosion, contamination etc.)
resulting from gases or materials the presence of which was unknown and agreed upon on
conclusion of contract.
A001061/34E 09-11 ©MTU